Quick answers
- Is CVE-2026-102075 exploited in the wild?
- No. Junglewise Threat Intelligence has no report of CVE-2026-102075 being exploited in the wild.
- How severe is CVE-2026-102075?
- High severity, with a CVSS score of 7.5, published 13 October 2026.
- Which products and versions are affected?
- Siemens APOGEE MBC (PPC) (BACnet) All versions; Siemens APOGEE MBC (PPC) (P2 Ethernet) All versions; Siemens APOGEE MEC (PPC) (BACnet) All versions; Siemens APOGEE MEC (PPC) (P2 Ethernet) All versions; and 6 more.
- Is there a fix for CVE-2026-102075?
- Yes: fixed in APOGEE PXC Compact (BACnet) V3.5.7 or later, APOGEE PXC Compact (P2 Ethernet) V2.8.21 or later, APOGEE PXC Modular (BACnet) V3.5.7 or later, APOGEE PXC Modular (P2 Ethernet) V2.8.21 or later, TALON TC Compact (BACnet) V3.5.7 or later, TALON TC Modular (BACnet) V3.5.7 or later. No fix planned for APOGEE MBC or APOGEE MEC variants.. Until then: Disable the FTP/Web service if not required for operations. Note that the web/FTP service is disabled by default on these products, so this mitigation applies only to deployments that have explicitly enabled it. Junglewise finds every place you run it, drafts the upgrade and applies it once you approve.
- How is CVE-2026-102075 attacked?
- It is attacked over the network, in a network appliance.
- Am I affected by CVE-2026-102075?
- Check whether you run Siemens APOGEE MBC (PPC) (BACnet), Siemens APOGEE MBC (PPC) (P2 Ethernet), Siemens APOGEE MEC (PPC) (BACnet) or one of the others listed at an affected version. Junglewise does that check for you around the clock: connect your code, cloud and domains, and it matches new vulnerabilities like this one against what you actually run and tells you when one reaches you.
How to fix
- Fixed in: APOGEE PXC Compact (BACnet) V3.5.7 or later, APOGEE PXC Compact (P2 Ethernet) V2.8.21 or later, APOGEE PXC Modular (BACnet) V3.5.7 or later, APOGEE PXC Modular (P2 Ethernet) V2.8.21 or later, TALON TC Compact (BACnet) V3.5.7 or later, TALON TC Modular (BACnet) V3.5.7 or later. No fix planned for APOGEE MBC or APOGEE MEC variants.
Disable the FTP/Web service if not required for operations. Note that the web/FTP service is disabled by default on these products, so this mitigation applies only to deployments that have explicitly enabled it.
Technical details
The web service in affected APOGEE MBC, MEC, PXC and TALON TC controllers fails to properly validate user input in multipart form data handling, allowing unauthenticated remote denial of service. Attack vector is network-based with no authentication required. The web/FTP service is disabled by default but can be enabled, making this a concern for deployments that activate these features.
Affected products
- Siemens APOGEE MBC (PPC) (BACnet) All versions
- Siemens APOGEE MBC (PPC) (P2 Ethernet) All versions
- Siemens APOGEE MEC (PPC) (BACnet) All versions
- Siemens APOGEE MEC (PPC) (P2 Ethernet) All versions
- Siemens APOGEE PXC Compact (BACnet) All versions < V3.5.7
- Siemens APOGEE PXC Compact (P2 Ethernet) All versions < V2.8.21
- Siemens APOGEE PXC Modular (BACnet) All versions < V3.5.7
- Siemens APOGEE PXC Modular (P2 Ethernet) All versions < V2.8.21
- Siemens TALON TC Compact (BACnet) All versions < V3.5.7
- Siemens TALON TC Modular (BACnet) All versions < V3.5.7
Timeline
- 2026-10-13: disclosed