Quick answers
- Is CVE-2026-102074 exploited in the wild?
- No. Junglewise Threat Intelligence has no report of CVE-2026-102074 being exploited in the wild.
- How severe is CVE-2026-102074?
- High severity, with a CVSS score of 7.5, published 13 October 2026.
- Which products and versions are affected?
- Siemens APOGEE MBC (PPC) (BACnet) All versions; Siemens APOGEE MBC (PPC) (P2 Ethernet) All versions; Siemens APOGEE MEC (PPC) (BACnet) All versions; Siemens APOGEE MEC (PPC) (P2 Ethernet) All versions; and 6 more.
- Is there a fix for CVE-2026-102074?
- Yes: fixed in APOGEE PXC Compact (BACnet) V3.5.7 or later; APOGEE PXC Compact (P2 Ethernet) V2.8.21 or later; APOGEE PXC Modular (BACnet) V3.5.7 or later; APOGEE PXC Modular (P2 Ethernet) V2.8.21 or later; TALON TC Compact (BACnet) V3.5.7 or later; TALON TC Modular (BACnet) V3.5.7 or later. Until then: Disable the FTP/Web service if not required for maintenance; note that this service is disabled by default on APOGEE and TALON products. Junglewise finds every place you run it, drafts the upgrade and applies it once you approve.
- How is CVE-2026-102074 attacked?
- It is attacked over the network, in a network appliance.
- Am I affected by CVE-2026-102074?
- Check whether you run Siemens APOGEE MBC (PPC) (BACnet), Siemens APOGEE MBC (PPC) (P2 Ethernet), Siemens APOGEE MEC (PPC) (BACnet) or one of the others listed at an affected version. Junglewise does that check for you around the clock: connect your code, cloud and domains, and it matches new vulnerabilities like this one against what you actually run and tells you when one reaches you.
How to fix
- Fixed in: APOGEE PXC Compact (BACnet) V3.5.7 or later; APOGEE PXC Compact (P2 Ethernet) V2.8.21 or later; APOGEE PXC Modular (BACnet) V3.5.7 or later; APOGEE PXC Modular (P2 Ethernet) V2.8.21 or later; TALON TC Compact (BACnet) V3.5.7 or later; TALON TC Modular (BACnet) V3.5.7 or later
Disable the FTP/Web service if not required for maintenance; note that this service is disabled by default on APOGEE and TALON products.
Technical details
The FTP service in affected Siemens controllers fails to validate the length of user-supplied input, enabling a denial-of-service attack through oversized input that crashes the service or device. An unauthenticated attacker on the network can trigger this condition remotely without authentication. The vulnerability affects multiple product lines; fixes are available for some (PXC/TALON devices) but not yet for APOGEE MBC/MEC.
Affected products
- Siemens APOGEE MBC (PPC) (BACnet) All versions
- Siemens APOGEE MBC (PPC) (P2 Ethernet) All versions
- Siemens APOGEE MEC (PPC) (BACnet) All versions
- Siemens APOGEE MEC (PPC) (P2 Ethernet) All versions
- Siemens APOGEE PXC Compact (BACnet) All versions < V3.5.7
- Siemens APOGEE PXC Compact (P2 Ethernet) All versions < V2.8.21
- Siemens APOGEE PXC Modular (BACnet) All versions < V3.5.7
- Siemens APOGEE PXC Modular (P2 Ethernet) All versions < V2.8.21
- Siemens TALON TC Compact (BACnet) All versions < V3.5.7
- Siemens TALON TC Modular (BACnet) All versions < V3.5.7
Timeline
- 2026-10-13: disclosed